Hello, I have a circuit that will need to return connected hardware to a default state if power is lost. The hardware can handle continuous voltage, so I’m thinking a simple solution would be to use a battery to provide that fallback power source. To avoid draining the battery, I’d like to connect it through a relay on the normally open contact and energize the relay directly from the main power supply on my board.

Do I need to look for anything in particular to make sure the coil on the relay I choose can sustain constant voltage for potentially months at a time without damage? Or, is there another similarly low cost and simple solution you’d recommend?

The circuit runs on 12VDC from a [Mean Well IRM-10-12 (specification), and the relays I have on hand are OMRON G5LE-14-CF 12VDC (specification). I don’t see anything on the relay documentation that specifies a maximum duty cycle.

  • @trafguy@midwest.socialOP
    link
    fedilink
    English
    11 year ago

    I’m a little new to the terminology, so to clarify, the switching current refers to the amperage across the terminals other than the coil, right? I’m definitely within those limits; I don’t expect to transfer more than ~1/8 of the maximum amperage.

    Is there a rule of thumb for the minimum current I should allow across the coil? The only specification I see on the datasheet for coil amperage is that it was tested to failure at 100mA. I don’t think power consumption is too big of a deal with this use case, but resistive heating sounds like it could shorten component life (and even if it’s only a secondary consideration here, I’d still prefer to minimize waste).

    • @empireOfLove
      link
      English
      21 year ago

      the switching current refers to the amperage across the terminals other than the coil

      Yes. “Switching current” is the load current being controlled across the main contacts. I figured you were well within specs, I was just clarifying what typically limits relay duty cycle other than the coil.

      Is there a rule of thumb for the minimum current I should allow across the coil?

      Stick to the rated coil voltage in the datasheet or below and you’ll be fine. They set the coil resistance to be within the safe current zone per V=IR at rated control voltage.

      Many relays can reliably switch well underneath their rated control voltage depending on their design- there’s a lot of safety factor built in. I’ve had some 12v automotive relays switch successfully at around 5v (by accident, lol). Experiment a bit and you may be able to cut down on waste power

      Just be aware that control voltage (coil) and rated switching voltage (load) is often different, since many relays use low control voltages to switch high voltage loads. Don’t confuse the two!