I’m a little wary of plug-in solar in the US. Some of the bills propose allowing 1200 watt panels which can overload wiring depending on what else is on the circuit and how in the wall wiring is run. Limiting plug-in panel wattage to, say, 400 watts might be necessary

  • A_Union_of_Kobolds@lemmy.world
    link
    fedilink
    arrow-up
    16
    ·
    16 hours ago

    I mean, yes. That’s how I make my living, im an electrician. But once again, supplying 10 amps is really not a risk in the majority of cases imo

    • silence7@slrpnk.netOP
      link
      fedilink
      arrow-up
      3
      ·
      16 hours ago

      My big concern is that somebody plugs a panel in plus two high-amp appliances, like a space heater and a microwave, in a sequence that means they don’t trip a breaker.

      • A_Union_of_Kobolds@lemmy.world
        link
        fedilink
        arrow-up
        25
        ·
        16 hours ago

        Microwave on a dedicated circuit above counter in kitchens and gfci protected per code

        You’re not putting a space heater on your kitchen counter

        And once again youre supplying up to 1200w, not drawing 1200w. Any power supply system will just be matching the load being drawn

        I really dont think this is the degree of a problem you think it is